Testing a MetroCluster configuration during FibreBridge 6500N bridge failure

To ensure that the MetroCluster configuration and the FibreBridge 6500N bridge are configured correctly, you must manually fail the bridge. Failure of the FibreBridge 6500N bridge must not initiate a disaster recovery and you must be able to access the data from both the nodes in the MetroCluster configuration.

You must have collected all the required information related to the components used in the MetroCluster configuration.
  1. Fail one FibreBridge 6500N bridge by powering it off.
  2. Verify that the data on both the nodes is accessible.
  3. Power on the bridge.
  4. Verify that the system returns to an healthy state and data on both the nodes is accessible.