Cabling the cluster interconnect

At each site, you must cable the cluster interconnect between the local controllers. If the local controllers are not configured as two-node switchless clusters, two-cluster switches are required.

About this task

This task must be performed at both MetroCluster sites.

Step

  1. Cable the cluster interconnect from one controller to the other, or, if cluster interconnect switches are used, from each controller to the switches.
    If the storage controller is a... Do this if using cluster interconnect switches... Do this if using a switchless cluster...
    FAS80xx Connect ports e0a through e0d on each controller to a local cluster interconnect switch. Connect ports e0a through e0d on each controller to the same ports on its HA partner.
    62xx Connect ports e0c and e0e on each controller to a local cluster interconnect switch. Connect ports e0c and e0e on each controller to the same ports on its HA partner.
    32xx Connect ports e1a and e2a on each controller to a local cluster interconnect switch. Connect ports e1a and e2a on each controller to the same ports on its HA partner.